Effect of Inner Diameter and Inclination Angles on Operation Limit of Closed-Loop Oscillating Heat-Pipes with Check Valves
P. Meena1, S. Rittidech1 & P. Tammasaeng1 Show affiliations
- Mahasarakham University, Thailand
American Journal of Engineering and Applied Sciences, Volume 1, Issue 2, pp. 100–103 · doi.org/10.3844/ajeassp.2008.100.103
Abstract
This research was to study the effect of inner diameter and inclination angles on operation limit of a closed loop oscillating heat pipes with check valves (CLOHP/CV). A set of CLOHP/CV was made of copper tubes in combination of following dimension: 1.77 and 2.03 mm inside diameter: 10 turn, with R123 was used as the working fluid. The working fluid was filled in the tube at the filling ratio of 50%. The inclination angles were 0, 20, 40, 60, 80 and 90° with 5 equal lengths for evaporator, adiabatic and condenser sections. The evaporator section was given heat by heater while the condenser section was cooled by volume water in a cold bath. The adiabatic section was properly insulated. In the test operation, it could be concluded as follows. It indicated that when the inner diameter changed from 1.77-2.03 mm the critical temperature increased. And when increase the inclination angles from 0 until to 90° the critical temperature increased.
Licence and reuse
Free to read. This article carries the publisher’s copyright, as printed on it: © 2008 Science Publications. It is free to read; ask us before reusing it.
How to reuse this articleResponses (0)
About this article
Meena, P., Rittidech, S. & Tammasaeng, P. (2008). Effect of Inner Diameter and Inclination Angles on Operation Limit of Closed-Loop Oscillating Heat-Pipes with Check Valves . American Journal of Engineering and Applied Sciences, 1(2), 100–103. https://doi.org/10.3844/ajeassp.2008.100.103
- Licence
- © Science Publications
- Issue
- Volume 1, Issue 2
- Policies
- Editorial independenceUse of generative AIData availabilityAppeals and complaints
- Version
- Version of record