Comparison of Losses and Flux Distribution in 3 Phase 100 kVA Distribution Transformers Assembled from Various Type of T-Joint Geometry
I. Daut, Dina M.M. Ahmad, S. Zakaria, S. Uthman & S. Taib
American Journal of Applied Sciences, Volume 3, Issue 9, pp. 1990–1992 · doi.org/10.3844/ajassp.2006.1990.1992
Abstract
This paper describes results of an investigation of the variation of power loss, building factor, flux leakage and flux distribution in 3-phase model transformer cores assembled from various type of T-joint geometry. The loss of the core with T-joint 60o was 10%, 12% and 15% better than the core with T-joint 45o, T-joint 23o and T-joint 90o respectively and 1.7 T, 50 Hz. The flux lines showed that flux penetration into the central limb was an important factor in causing the differences in performance.
Licence and reuse
Free to read. This article carries the publisher’s copyright, as printed on it: © 2006 Science Publications. It is free to read; ask us before reusing it.
How to reuse this articleResponses (0)
About this article
Daut, I., Ahmad, D. M., Zakaria, S., Uthman, S. & Taib, S. (2006). Comparison of Losses and Flux Distribution in 3 Phase 100 kVA Distribution Transformers Assembled from Various Type of T-Joint Geometry. American Journal of Applied Sciences, 3(9), 1990–1992. https://doi.org/10.3844/ajassp.2006.1990.1992