Supplying a Common Distribution Load through Two Different Sources
M. H. Naeem & K. P. Basu
American Journal of Applied Sciences, Volume 2, Issue 9, pp. 1305–1308 · doi.org/10.3844/ajassp.2005.1305.1308
Abstract
Phase angle difference between any two Busbar voltages of a big power system varies with the loading and operating condition of the power system. Supplying a common distributed load from these two phase shifted sources needs the application of a controlled phase shifter. Three-phase tapped autotransformer connected in delta with properly controlled variation of input and output tap settings may perform the function of this type of phase shifter. Both on-load and off-load tap changing may be used to control the phase angle for scheduled sharing of a common distribution load between these two phase shifted sources. Independent control of voltage magnitude is also possible through the same phase shifter.